Appendix 1 Error Codes
761
A
Codes of errors detected by other than the self-diagnostic function (4000H to 4FFFH)
The following table lists the codes of errors, other than those detected by the self-diagnostic function of the CPU module.
Error codes returned to request source during communications with the CPU module
Errors generated when the data communications are requested from the engineering tool, intelligent function module, or
network system connected
Errors generated with the data logging function
These error codes are not stored in SD0 because they are not detected by the self-diagnostic function of the CPU module.
Error
code
Error name Error details and cause Action
4000H Common error Serial communication sum check error Connect the serial communication cable correctly.
Take measures to reduce noise.
4001H Common error An unsupported request was executed.
(The request was executed to the CPU module that does not
support the request.)
Check the command data of the SLMP/MC protocol.
Check the CPU module model name selected in the
engineering tool.
Check the target CPU module model name.
4002H Common error An unsupported request was executed. Check the command data of the SLMP/MC protocol.
Check the CPU module model name selected in the
engineering tool.
Execute the request again.
If the same error code is displayed again, the possible cause
is a hardware failure of the CPU module. Please consult
your local Mitsubishi representative.
4003H Common error Command for which a global request cannot be performed
was executed.
Check the command data of the SLMP/MC protocol.
4004H Common error All the operations to the CPU module are disabled because of
the following reason:
The CPU module is starting up.
Perform operations to the CPU module again after the start-
up processing ends.
4005H Common error The amount of data handled according to a specified
request is out of range.
Check the command data of the SLMP/MC protocol.
4006H Common error Initial communication has failed. When using serial communication, inquire of the external
device manufacturer for support conditions.
When using serial communication, check the CPU module
model name selected in the engineering tool.
When using Ethernet communication, shift the
communication start timing.
4008H Common error The CPU module is BUSY. (The buffer is not vacant.) Execute the request again after the specified period of time
has elapsed.
400BH Common error A set value of data handled according to a specified request
is invalid.
Check the request data of a dedicated instruction.
Check the command data of the SLMP/MC protocol.
4010H CPU module
operation error
The request cannot be executed because the CPU module
is running.
Set the operating status of the CPU module to STOP, and
execute the request again.
4013H CPU module
operation error
The request cannot be executed because the CPU module
is not in the STOP state.
Set the operating status of the CPU module to STOP, and
execute the request again.
4021H File related error The specified drive (memory) does not exist or there is an
error.
Check the specified drive (memory) status.
Back up data in the CPU module, and then initialize the
memory.
4022H File related error The file with the specified file name or file No. does not exist.
The specified program block does not exist.
When CPU Module Logging Configuration Tool is used
The data logging was started in the following state.
A program name (program No.) that does not exist was
specified.
Check the specified file name and file No.
Check the specified program block name.
When CPU Module Logging Configuration Tool is used
Check the specified program name.
4023H File related error The file name and file No. of the specified file do not match. Delete the file and then recreate the file.
4024H File related error The specified file cannot be handled by a user. Do not access the specified file.
4025H File related error The specified file is processing the request from another
engineering tool.
Forcibly execute the request. Or, execute the request again
after the processing being performed ends.
4026H File related error The file password set in advance to the target drive
(memory) must be specified.
Specify the file password set in advance, and then access to
the drive (memory).
4027H File related error The specified range is larger than the file size. Check the specified range and access within that range.
4028H File related error The same file already exists. Forcibly execute the request. Or, change the file name and