EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R-R04CPU - Page 764

Mitsubishi Electric MELSEC iQ-R-R04CPU
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
762
APPX
Appendix 1 Error Codes
4029H File related error The specified file capacity cannot be obtained. Review the specified file capacity, and execute the request
again.
402AH File related error The specified file is abnormal. Back up data in the CPU module, and then initialize the
memory.
402BH File related error The request cannot be executed in the specified drive
(memory).
Set the operating status of the CPU module to STOP, and
execute the request again.
402CH File related error The request cannot be executed currently. Execute the request again after a while.
402FH File related error Writing of a file did not complete. Back up data internally in the CPU module, and delete the
corresponding file or initialize the drive 4. Then, write the file
to the programmable controller again.
Write the program restoration information. Then, read the
program files from the programmable controller again.
4030H Device
specification
error
The specified device is not supported.
When CPU Module Logging Configuration Tool is used
The data logging specifying a device that is not supported
was started.
Check the specified device.
4031H Device
specification
error
The specified device number is out of range.
The CPU module does not support the specified device.
When CPU Module Logging Configuration Tool is used
The data logging specifying a device number that does not
exist was started.
Check the specified device number.
Check the device assignment of the CPU module.
Check the specified device.
4032H Device
specification
error
The device modification was incorrectly specified. Or, the
unusable device (TS, TC, SS, SC, CS, or CC) was specified
in any of the following SLMP/MC protocol commands; Read
random, Write random (in units of words), Entry monitor
device, or Execute monitor.
When CPU Module Logging Configuration Tool is used
The data logging specifying a device modification that is not
supported was started.
Check the device modification method.
Check the specified device.
4033H Device
specification
error
Writing cannot be done because the specified device is for
system use.
Do not write the data in the specified device, and do not turn
on or off.
4034H Device
specification
error
The dedicated instruction cannot be executed since the
completion device for the dedicated instruction does not turn
on.
Since the completion device for the SREAD or SWRITE
instruction does not turn on in the CPU module on the target
station, execute the instruction again after setting the
operating status of the CPU module on the target station to
the RUN status.
4040H Intelligent
function module
specification
error
The request cannot be executed to the specified intelligent
function module.
Check whether the specified module is the intelligent
function module having the buffer memory.
4041H Intelligent
function module
specification
error
The access range exceeds the buffer memory range of the
specified intelligent function module.
Check the start address and access number of points and
access using a range that exists in the intelligent function
module.
4042H Intelligent
function module
specification
error
The specified intelligent function module cannot be
accessed.
Check that the specified intelligent function module is
operating normally.
Check the specified module for a hardware fault.
4043H Intelligent
function module
specification
error
The intelligent function module does not exist in the
specified position.
When CPU Module Logging Configuration Tool is used
The data logging specifying a device that does not exist or
cannot be accessed was started.
Check the I/O number of the specified intelligent function
module.
4044H Intelligent
function module
specification
error
A control bus error occurred during access to the intelligent
function module.
Check the specified intelligent function module and other
modules and base units for a hardware fault.
4049H Intelligent
function module
specification
error
A request cannot be processed because the module
extension parameter of the positioning module is being used
for the positioning control.
Turn off module ready (Yn+0) of the positioning module or
execute the processing again after removing the extension
parameter of the positioning module from the target data.
4050H Protect error The request cannot be executed because the write protect
switch of the SD memory card is on.
Turn off the write protect switch.
Error
code
Error name Error details and cause Action

Table of Contents

Related product manuals