EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-RJ71EIP91 - Page 36

Mitsubishi Electric MELSEC iQ-RJ71EIP91
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
1 FUNCTIONS
1.1 EtherNet/IP Communication Functions
Application Trigger and Change of State
Data sending with Application Trigger or Change of State is executed by turning off and on 'Application Trigger Request
(Class1)' (Un\G27008 to Un\G27023).
When data is sent with Application Trigger, whether or not to send the data automatically can be selected by 'Application
Trigger operating specification Request (Class1)' (Un\G16631). When data is sent with Change of State, this setting is
ignored.
The following table lists the setting items of Application Trigger and Change of State.
*1 When Default is set, a quarter of RPI is specified as the inhibit time.
*2 When Un-Activated is set, no inhibit time is specified.
Type Setting item of EtherNet/IP Configuration Tool Buffer memory
Trigger Type Inhibit time setting 'Application Trigger Request
(Class1)' (Un\G27008 to Un\G27023)
Inhibit Time Mode Inhibit time(ms)
Application Trigger Application (No setting) (No setting) Off On
Change of State Change of State Default
*1
(No setting) Off On
Un-Activated
*2
(No setting) Off On
Custom Specifies in the range
between 1 and 255.
Off On

Table of Contents