EasyManua.ls Logo

Mitsubishi Electric Melsec QJ71LP21 - Page 371

Mitsubishi Electric Melsec QJ71LP21
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 - 147 7 - 147
MELSEC-Q
7 APPLICATION FUNCTIONS
(b) Cyclic transmission
Station No. 4
Host station
send range
Station No. 1 (2)
Received data
Received data
Station No. 3
Host station
send range
Station No. 3
Received data
Station No. 4
Received data
Station No. 3
Received data
Station No. 4
Received data
Station No. 3
Host station
send range
Station No. 1 (2)
Received data
Station No. 4
Received data
Redundant system
2)
2)
0000
H
00FFH
0100
H
01FFH
0200
H
02FF
H
1)
1)
Host station
send range
1) Station No. 2 takes over the host station send range data handled by station No. 1 (data tracked)
and sends them to other stations without discontinuing a data link.
2) Station No. 2 receives data from other stations.
[When station No. 1 is cut off due to a communication error (system switching occurs)]
If a communication error occurs in station No. 1 and it is consequently cut off from the network, the network module automatically
issues a system switching request to the control system CPU, and system switching occurs in the redundant system.
After system switching, station No. 2, a new control system, continues a data link.
Cyclic transmission after system switching in the redundant system is shown below.
Station No. 2
(control system)
Station No. 1
(standby system)

Table of Contents

Related product manuals