2 SPECIFICATIONS
2.1 General Specifications
15
2
2 SPECIFICATIONS
This chapter describes the specifications of the IO-Link module.
2.1 General Specifications
*1 Do not use or store the IO-Link module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause
malfunction. When using the IO-Link module under pressure, please consult your local Mitsubishi representative.
*2 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the module can be
used even outside the control panel.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to
the rated voltage of 300V is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
*5 Use the special coated products which comply with the IEC 60721-3-3 3C2 in the environment with the corrosive gases. For details on
the special coated products, please consult your local representative.
*6 When the programmable controller is used at altitude above 2000m, the withstand voltage performance and the upper limit of the
operating ambient temperature decrease. Please consult your local Mitsubishi representative.
To use the IO-Link module complying with the EMC Directive, refer to "EMC and Low Voltage Directives" in
this manual. ( Page 193 EMC and Low Voltage Directives)
Item Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
Operating ambient
humidity
5 to 95%RH, non-condensing
Storage ambient
humidity
Vibration resistance Compliant with JIS
B 3502 and IEC
61131-2
Frequency Constant
acceleration
Half amplitude Sweep count
Under intermittent
vibration
5 to 8.4Hz 3.5mm 10 times each in X,
Y, and Z directions
8.4 to 150Hz 9.8m/
Under continuous
vibration
5 to 8.4Hz 1.75mm
8.4 to 150Hz 4.9m/
Shock resistance Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gases
*5
, flammable gases, less conductive dust
Operating altitude
*1
0 to 2000m
*6
Installation location Inside a control panel
*2
Overvoltage
category
*3
or less
Pollution degree
*4
2 or less
Equipment class Class