5 INSTALLATION AND WIRING
5.5 Wiring
35
5
5.5 Wiring
Wiring with terminal block for module power supply and FG
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range.
Tightening the screw too much may damage the IO-Link module case.
Wire to be used
The following describes the wire to be connected to the terminal block for module power supply and FG.
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screw with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screw with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
Screw type Tightening torque range
Terminal block mounting screw (M2.5 screw) 0.2 to 0.3Nm
Diameter Type Material Temperature rating
20 to 14 AWG Core Copper wire 75 or more
Product name Model Applicable wire size Bar solderless terminal
tool
Contact
Bar solderless terminal AI 0.5-8WH, AI 0.5-10WH 0.5 CRIMPFOX6 PHOENIX CONTACT GmbH & Co. KG
AI 0.75-8GY, AI 0.75-10GY 0.75
AI 1-8RD, AI 1-10RD 1.0
AI 1.5-8BK, AI 1.5-10BK 1.5
Al 2.5-10BU 2.0