5 INSTALLATION AND WIRING
5.2 Setting Switch
29
5
5.2 Setting Switch
Setting station number setting switches
Setting procedure
Set the station number using the rotary switches on the front of the IO-Link module. The set value of the station number
becomes valid when the module is powered on. Thus, set the station number while the module power is off.
The hundreds and tens places of the station number are set with 10.
The ones place of the station number is set with 1.
To set the station number setting switches, use a flathead screwdriver with a tip width of 3.5mm or less.
Ex.
To set the station number to 115, set the switches as shown below.
Setting range
Set the station number from 1 to 120. Setting the value other than 1 to 120 causes a communication error and the D LINK
LED flashes.
Do not set a station number duplicated with other station numbers. If the station number is duplicated, a
communication error occurs and the D LINK LED does not turn on.