2 - 75
2 SYSTEM CONFIGURATION
2.5.9 Forced stop input terminal
(1) Table of the forced stop input terminal specifications
Item Specifications
Number of input points Forced stop signal : 1 point
Input method Sink/Source type
Rated input current 2.4mA
Isolation method Photocoupler
Operating voltage range
20.4 to 26.4VDC
(+10/ -15%, ripple ratio 5% or less)
ON voltage/current 17.5VDC or more/2.0mA or more
OFF voltage/current 1.8VDC or less/0.18mA or less
Input resistance Approx. 10k
Response time
OFF to ON
1ms or less
ON to OFF
External connector type 3 pin connector
Recommended wire size
0.3 to 1.5mm
2
(AWG16 to AWG22)