EasyManua.ls Logo

Mitsubishi Electric Q170MSCPU - Battery Life

Mitsubishi Electric Q170MSCPU
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 - 8
6 INSPECTION AND MAINTENANCE
6.5.1 Battery life
The battery life is shown below.
Table 6.4 Battery life of Q6BAT/Q7BAT
Motion controller Battery type
Battery
consumption
(Note-1)
Battery life (Total power failure time) [h]
(Note-2)
Power-on
time ratio
(Note-3)
Guaranteed
value
(Note-4)
(MIN)
(75°C (167°F))
Guaranteed
value
(Note-5)
(TYP)
(40°C (104°F))
Actual service
value
(Note-6)
(Reference value)
(TYP)
(25°C (77°F))
Backup time
after alarm
(Note-7)
Q170MSCPU
(Note-8)
Q6BAT
(Note-9)
2
0% 13000 40000
43800
90
(After SM51/
SM52 ON)
30% 18000
43800
50% 21000
70% 24000
100% 43800
Q6BAT
(Note-9)
(Large capacity)
2
0% 39000
43800
30%
43800
50%
70%
100%
Q170MSCPU-S1
Q6BAT
(Note-9)
1
0% 15300
30% 21000
50% 27900
70% 41500
100% 43800
2
0% 2600 7500 8800
30% 3700 10600 12500
50% 5100 14700 17400
70% 8400 23700 28000
100% 43800 43800 43800
3
0% 1400 4100 4800
30% 2100 5900 6900
50% 2900 8200 9600
70% 4800 13500 15800
100% 43800 43800 43800

Table of Contents

Other manuals for Mitsubishi Electric Q170MSCPU

Related product manuals