517
APPENDICES
A
Appendix 3 List of Special Register Areas
SD81
Continuation
error cause
Continuation
error cause
This register stores a continuation error cause.
QnUDVCPU: The b9 is fixed to 0.
LCPU: The b14 and b15 are fixed to 0.
S (Error) New
QnUDV
LCPU
SD82
Continuation
error cause
Continuation
error cause
This register stores a continuation error cause.
(1)UNIT VERIFY ERR.
(2)MULTI CPU ERROR
(3)Fixed to 0
LCPU: All bits are fixed to 0.
S (Error) New
QnUDV
*10
LCPU
*10
This register stores a continuation error cause.
(1)UNIT VERIFY ERR.
(2)MULTI CPU ERROR
(3)PID ERROR
(4)Fixed to 0
LCPU: The b0 and b1 are fixed to 0.
QnUDV
*9
LCPU
*9
SD84
Continuation
error clear
Continuation
error clear
This register stores a continuation error to be cleared in bit
pattern.
For the LCPU, all bits are empty.
UNew
QnUDV
LCPU
SD85
SD90
Step
transition
monitoring
timer setting
value
(Enabled
only when
SFC program
exists)
F number for
timer set
value and
time over
error
Corresponds to
SM90
This register stores a value set for step
transition monitoring timer and the
number of an annunciator (F) that
turns on if the monitoring timer times
out.
Turning on any of SM90 to SM99 while
a step is running will start the timer,
and if the transition condition for the
step next to the active step is not met
within the timer limit, the set
annunciator (F) turns on.
U
D9108
Qn(H)
QnPH
QnPRH
SD91
Corresponds to
SM91
D9109
SD92
Corresponds to
SM92
D9110
SD93
Corresponds to
SM93
D9111
SD94
Corresponds to
SM94
D9112
SD95
Corresponds to
SM95
D9113
SD96
Corresponds to
SM96
D9114
SD97
Corresponds to
SM97
NewSD98
Corresponds to
SM98
SD99
Corresponds to
SM99
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
D9
Corresponding
CPU
SD81
b15 b11b12 b7b8 b3b4 b0
SP.UNIT DOWN
AC/DC DOWN
BATTERY ERROR
FLASH ROM ERROR
SP.UNIT ERROR
ICM.OPE.ERROR
FILE OPE.ERROR
REMOTE PASS.FAIL
SNTP OPE.ERROR
DISPLAY ERROR
OPERATION ERROR
PRG.TIME OVER
F***(Annunciator)
FUSE BREAK OFF
SINGLE PS.DOWN
SINGLE PS.ERROR
SD82
b15 b11b12 b7b8 b3b4 b0
(3)
(1)(2)
SD82
b15 b11b12 b7b8 b3b4 b0
(4)
(3) (1)(2)
b15 b7 b0b8
F number setting
(0 to 255)
Timer time limit
setting
(1 to 255s:
(1s units))
to to