11. TROUBLESHOOTING
11 - 15
MELSEC-
A
Table 11.1 Error codes (Continue)
Error Message
Error
Code
(D9008)
Detailed
Error
Code
(D9092)
CPU
States
Error and Cause Corrective Action
(1) The result of BCD conversion
exceeds the rated range ("9999"
or "99999999").
(2) There is a setting exceeding the
rated device range, disabling
execution of calculation.
(3) The file register is used on the
program without designation of
the capacity of the file register.
Use the peripheral device to read and
correct the error step in the program.
(Check the setting range of the device,
BCD conversion value and so on.)
503 The data stored by the designated
device or a constant exceeds the
allowable range.
504 The setting quantity of handled data
exceeds the allowable range.
Use the peripheral device to read and
correct the error step in the program.
The number of special instructions for
CC-Link executed in each scan
exceeds 64.
Reduce the special instructions for
CC-Link executed in each scan to
within 64.
"OPERATION
ERROR"
50
509
Stop
or
Contin
ue
(set by
para-
meter)
A special instruction for CC-Link is
executed to a CC-Link module to
which no parameter is defined.
Define parameters.
"BATTERY
ERROR"
70 Contin
ue
(1) The battery voltage is low.
(2) The battery lead connector is not
connected.
(1) Replace the battery.
(2) Connect the lead connector to
use the built-in RAM memory or
power failure compensation
function.