EasyManua.ls Logo

Mitsubishi A1SJH - Page 150

Mitsubishi A1SJH
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDICES
APP - 16
MELSEC-
A
Table 2.1 Special relay list (Continue)
Number Name Description Details Applicable CPU
M9180
Active step
sampling trace
complete flag
OFF: Trace start
ON: Trace complete
• Turned on when sampling trace of all specified
blocks is completed. Turned off when sampling trace
is started.
Usable with AnN ,
AnA
, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
M9181
Active step
sampling trace
execution flag
OFF: Trace not executed.
ON: Trace being
executed.
• Turned on when sampling trace is being executed.
Turned off when sampling trace is completed or
suspended.
Usable with AnN ,
AnA
, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
2
M9182
Active step
sampling trace
enable
OFF: Trace
disable/suspend
ON: Trace enable
• Selects sampling trace execution enable/disable.
ON: Sampling trace execution is enabled.
OFF: Sampling trace execution is disabled.
If turned off during sampling trace execution,
trace is suspended.
Usable with AnN ,
AnA
, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
2
M9196
Operation output
at block stop
OFF: Coil output off
ON: Coil output on
• Selects the operation output when block stop is
executed.
ON: Retains the ON/OFF status of the coil being
used by using operation output of the step
being executed at block stop.
OFF: All coil outputs are turned off. (Operation
output by the SET instruction is retained
regardless of the ON/OFF status of M9196.)
Usable with AnN ,
AnA
, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
M9197
M9198
I/O numbers
to be
displayed
OFF OFF X/Y0 to 7F0
M9197
ON OFF X/Y800 to FF0
OFF ON
X/Y1000 to
17F0
M9198
Fuse blow, I/O
verify error
display switching
ON ON
X/Y1800 to
1FF0
• Switches I/O numbers in the fuse blow module
storage registers (D9100 to D9107) and I/O module
verify error storage registers (D9116 to D9123)
according to the combination of ON/OFF of the
M9197 and M9198.
Usable with AnU,
A2AS and QCPU-A
(A Mode)
M9199
Data recovery of
online sampling
trace / status
latch
OFF: Data recovery OFF
ON: Data recovery ON
• When sampling trace / status latch is executed, the
setting data stored in the CPU module is recovered
to enable restart.
• Turn on M9199 to execute again.
(There is no need to write data with the peripheral
device.)
Usable with AnU,
A2AS and QCPU-A
(A Mode)
: Usable with AnN and AnA which are compatible with SFC.
For the AnN and AnA which are compatible with SFC, refer to the MELSAP-II Programming Manual.

Table of Contents