5-6
4.
Detailed settings are displayed after the manufacturer, controller type, I/F, and driver are congured.
Item Description Range
Baud rate
Set this item when change the baud rate used for
communication with the connected equipment.
(Initial value: 19200bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data length
Set this item when change the data length used for
communication with the connected equipment.
(Initial value: 7bits)
7bits/8bits
Stop Bit
Specify the stop bit length for communications.
(Initial value: 1bit)
1bit/2bits
Parity
Specify whether or not to perform a parity check, and
how it is performed during communication.
(Initial value: odd)
None
Even
Odd
Retry
Set the number of retries to be performed when a
communication timeout occurs.
(Initial value: 0time)
0 to 5times
Timeout Time
Set the time period for a communication to time out.
(Initial value: 3sec)
1 to 30sec
Delay Time
Set this item to adjust the transmission timing of the
communication request from the GOT.
(Initial value: 10ms)
0 to 300ms
* Initial values are the initial settings of parameters from the factory.
Although the inverter can be operated at the initial settings, congure parameters in accordance with your
usage environment.