F-7
2 Specifications
2.3 Performance Specifications
FX
3U
/FX
3UC
Series PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
A
Common Items
B
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3U
-4DA-ADP
E
FX
3U
-4AD-PT
-ADP
F
FX
3U
-4AD-TC
-ADP
G
PID Instruction
(FNC 88)
2.3 Performance Specifications
Item
Specifications
Centigrade (
°
C) Fahrenheit (
°
F)
Input signal
Thermocouple type K or J
JIS C 1602-1995
Rated temperature
range
Type K
-100
°
C to +1000
°
C
Type K
-148
°
F to +1832
°
F
Type J
-100
°
C to +600
°
C
Type J
-148
°
F to +1112
°
F
Digital output
Type K -1000 to +10000 Type K -1480 to +18320
Type J -1000 to +6000 Type J -1480 to +11120
Resolution
Type K
0.4
°
C
Type K
0.72
°
F
Type J
0.3
°
C
Type J
0.54
°
F
Total accuracy
±(0.5% full scale +1
°
C)
A/D conversion
time
200µs (The data will be updated at every scan time.)
For a detailed description of data update, refer to Section2.4.
Input
characteristics
Insulation method
The photo-coupler is used to insulate the analog input area from the PLC.
The DC/DC converter is used to insulate the driving power supply line from the analog
input area.
Channels are not insulated from each other.
Number of I/O
occupied points
0 point
(This number is not related to the maximum number of input/output points of the PLC.)
0
+1000
°
C
+10000
-100
°
C
-1000
Approx.
-110°C
Approx.
+1010°C
+10100
-1100
Type K
0
+600
°
C
+6000
-100
°
C
-1000
Approx.
-110°C
Approx.
+610°C
+6100
-1100
Type J
0
+18320
-1480
+18500
-1660
Type K
Approx.
+1850
°
F
+1832
°
F
-148
°
F
Approx.
-166
°
F
0
+11120
-1480
+11300
-1660
Type J
Approx.
+1130°F
+1112
°
F
-148
°
F
Approx.
-166°F

Table of Contents