A-29
4 Comparison of Performance Specifications
4.4 Temperature Sensor Input
A
Common Items
B
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3U
-4DA-ADP
E
FX
3U
-4AD-PT
-ADP
F
FX
3U
-4AD-TC
-ADP
G
PID Instruction
(FNC 88)
FX
3U
/FX
3UC
Series PLC User's Manual - Analog Control Edition
Common Items
4.4.4 FX2N-4AD-TC
Specifications
FX2N-4AD-TC
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
Input signal
Thermocouple type K or J
JIS C 1602-1995
Rated temperature range
Type K: -100°C to +1200°C
Type J: -100°C to +600°C
Type K: -148°F to +2192°F
Type J: -148
°
F to +1112°F
Digital output
Type K: -1000 to +12000
Type J: -1000 to +6000
Type K: -1480 to +21920
Type J: -1480 to +11120
Resolution
Type K: 0.4°C
Type J: 0.3°C
Type K: 0.72°F
Type J: 0.54°F
Overall accuracy ±(0.5% for full scale +1°C)
Time required for
conversion
(240ms±2%)× number of selected channels
Input characteristics
Insulation method
The photocoupler is used to insulate the analog input area from the PLC.
The DC/DC converter is used to insulate the power supply from the analog inputs.
Channels are not insulated from each other.
Number of I/O occupied
points
8 points (Count either the input or output points of the PLC.)
0
+12000
(Type K)
+1200°C
(Type K)
-100°C
-1000
+600°C
(Type J)
+6000
(Type J)
0
+11120
(Type J)
+2192
°
F
(Type K)
-148
°
F
-1480
+21920
(Type K)
+1112
°
F
(Type J)