2 Description of Analog Products
2.2 List of Analog Product Models
FX
3U
/FX
3UC
Series PLC User's Manual - Analog Control Edition
Common Items
2.2 List of Analog Product Models
Voltage/current input/output mixture
FX2N-5A
*1
Input
4ch
Voltage:
-10V to +10V DC
0.32mV
(with sign, 16 bits)
Mixed use of voltage and current
is possible.
The offset/gain can be adjusted.
The scaling function is
incorporated.
*2
Current:
-20mA to +20mA DC
1.25µA
(with sign, 15 bits)
Output
1ch
Voltage:
-10V to +10V DC
5mV
(with sign, 12 bits)
Current:
0mA to 20mA DC
20µA
(10bits)
FX
0N-3A
*1
Input
2ch
Voltage:
0V to 10V DC
40mV
(8bits)
The input format is common to 2
channels.
The offset/gain can be adjusted.
(Common to 2 input channels)
*2
Current:
4mA to 20mA DC
64µA
(8bits)
Output
1ch
Voltage:
0V to 10V DC
40mV
(8bits)
Current:
4mA to 20mA DC
64µA
(8bits)
Temperature sensor input
FX2N-8AD
*1
8ch
Type K:
-100°C to +1200°C
0.1°C
Mixed use of voltage, current,
and thermocouple is possible.
Compatible with thermocouple
types K, J, and T.
The unit can be switched
between "centigrade" and
"Fahrenheit."
The sampling function is
incorporated.
*2
Type J:
-100°C to +600°C
0.1°C
Type T:
-100°C to +350°C
0.1°C
FX
2N-4AD-TC
*1
4ch
Type K:
-100°C to +1200°C
0.4°C
Compatible with thermocouple
types K and J.
The unit can be switched
between "centigrade" and
"Fahrenheit."
*2
Type J:
-100°C to +600°C
0.3°C
FX
2N-4AD-PT
*1
4ch
Pt100:
-100°C to +600°C
0.2°C to 0.3°C
Compatible with the platinum
resistance thermometer sensor
(Pt100 or JPt100).
The unit can be switched
between "centigrade" and
"Fahrenheit."
*2
FX
2N-2LC
*1
2ch
Example:
Type K:
-100°C to +1300°C
0.1°C or 1°C
(Depends on the
sensor input range.)
Compatible with thermocouple
types K, J, R, S, E, T, B, N, PL II,
WRe5-26, U, and L.
Compatible with the platinum
resistance thermometer sensor
(Pt100, JPt100).
The unit can be switched
between "centigrade" and
"Fahrenheit."
The temperature adjustment
function (that uses PID operation,
etc.) is incorporated.
The peak disconnection
detection function is
incorporated.
(The CT sensor is needed.)
*2
Pt100:
-200°C to +600°C
*1. To connect this block to the FX3UC Series PLC, either FX2NC-CNV-IF or FX3UC-1PS-5V is needed.
*2. Refer to the instruction manual of the corresponding product.
Type
No. of
channels
Range Resolution Function
Refer-
ence

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-F FX3U Series and is the answer not in the manual?

Mitsubishi MELSEC-F FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-F FX3U Series
CategoryController
LanguageEnglish

Related product manuals