6-10
ED=,ED<>,ED>,ED<=,ED<,ED>=
Caution
(1) Since the number of digits of the real number that can be input by Programing Tool is up to
15 digits, the comparison with the real number whose number of significant digits is 16 or
more cannot be made by the instruction shown in this section.
When judging match/mismatch with the real number whose significant digits is 16 or more by
the instruction in this section, compare it with the approximate values of the real number to
be compared and judge by the sizes.
When judging the match of E1.234567890123456+10 (Number of significant
digits is 16) and the double-precision floating-point data.
When judging the mismatch of E1.234567890123456+10 (Number of significant
digits is 16) and the double-precision floating-point data.
Example
E1.234567890123456+10
E1.23456789012345+10
E1.23456789012346+10
Whether D0 to D3 is within this range is checked.(Values on boundaries are excluded.
)
Example
E1.234567890123456+10
Whether D0 to D3 is within this range is checked.(Values on boundaries are included.)
E1.23456789012345+10
E1.23456789012346+10

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals