7-408
7.18.10 Reading module model name (TYPERD(P))
.
Set Data
*1: Universal model QCPU only.
Function
(1) This instruction reads the module information stored in the area starting from the I/O number
specified by "n", and stores it in the area starting from the device specified by .
The following 6 modules (Q series only) support the instruction.
•CPU module
• Input module
• Output module
• I/O combined module
• Intelligent function module
• GOT (bus connection)
For the LCPU, the following four models are supported.
•CPU module
• Input module
• Output module
• Intelligent function module
Universal model QCPU: The serial number (first five digits) is "11043" or later.
Setting
data
Internal device
R, ZR
J\
U\G
Zn
Constant
K, H
Others
Bit
Word
*6
Bit Word
n –– –– ––
–– –– –– ––
Setting data Description Setting range Set by Data type
n
Value obtained by dividing the start I/O number of a module
whose model name is to be read by 16
0 to FFH,
3E0 to 3E3H
*1
User BIN 16 bits
+0
Execution result of the instruction
Within each
device range
System
BIN 16 bits
+1 to +9
Module model name Character string
Basic
Process
High
performance
Redundant
Ver.
Universal
LCPU
TYPERD
TYPERDP
Command
Command
TYPERD D
n
TYPERDP
D
n
D
D
D
D D
D

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals