7-262
ASIN(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
• The value designated by is outside the range of from 1.0 to 1.0. (Error code: 4100)
• The contents of the designated device or the result of the addition are not "0", or not within
the following range(For the Universal model QCPU, LCPU): (Error code: 4140)
0, 2
-126
| Contents of designated device | < 2
128
• The value of the specified device is 0.
*2
(For the High Performance model QCPU, Process CPU, Redundant CPU)
(Error code: 4100)
*2: There are CPU modules that will not result in an operation error if 0 is specified. Refer to 3.2.4 for details.
• The result exceeds the following range (Operation results in an overflow)
(For the Universal model QCPU, LCPU)
2
128
| Operation result | (Error code: 4141)
• The value of the specified device is 0, unnormalized number, nonnumeric, and ± .
(For the Universal model QCPU, LCPU) (Error code: 4140)
S

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals