12-7
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.3 Error code list (1000 to 1999)
1009
[MAIN CPU DOWN]
• The power supply module detected an incorrect
power waveform.
• When using the redundant base unit, the
redundant power supply module failure in both
systems and/or the redundant base unit failure
are detected.
• The voltage waveform that is outside the
specification was applied to the power supply
module.
â– Collateral information
• Common Information:-
• Individual Information:-
â– Diagnostic Timing
• Always
• Correct the voltage waveform applied to the
power supply module.
• Reset the CPU module and run it again. If the
same error code is detected again, the cause is
a failure of the power supply module, CPU
module, main base unit, extension base unit, or
extension cable. (Please consult your local
Mitsubishi representative, explaining a detailed
description of the problem.)
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00J/Q00/Q01
*8
Qn(H)
*10
QnPH
QnPRH
QnU
[CPU UNIT DOWN]
• A failure was detected on the power supply
module or CPU module.
• The voltage waveform that is outside the
specification was applied to the power supply
module.
â– Collateral information
• Common Information:-
• Individual Information: Failure information
• Diagnostic Timing
• Always
• Correct the voltage waveform applied to the
power supply module.
• Reset the CPU module and run it again.
• If the same error code is displayed again, the
cause is a hardware failure of the power supply
module or CPU module. (Please consult your
local Mitsubishi representative, explaining a
detailed description of the problem.)
LCPU
1010
[END NOT EXECUTE]
Entire program was executed without the
execution of an END instruction.
• When the END instruction is executed it is read
as another instruction code, e.g. due to noise.
• The END instruction has been changed to
another instruction code somehow.
â– Collateral information
• Common Information:-
• Individual Information:-
â– Diagnostic Timing
• When an END instruction executed
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a hardware failure of the CPU module. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
QCPU
LCPU
1020
[SFCP. END ERROR]
The SFC program cannot be normally terminated
due to noise or other reason.
• The SFC program cannot be normally
terminated due to noise or any similar cause.
• The SFC program cannot be normally
terminated for any other reason.
â– Collateral information
• Common Information:-
• Individual Information:-
â– Diagnostic Timing
• When SFC program is executed
Q00J/Q00/Q01
*8
QnPH
QnU
LCPU
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU