12.1 Error Code List
12.1.7 Error code list (5000 to 5999)
5010
[PRG. TIME OVER]
• The program scan time exceeded the constant
scan time specified in the PLC RAS tab of the
PLC Parameter dialog box.
â– Collateral information
• Common information: Time (value set)
• Individual information: Time (value actually
measured)
â– Diagnostic Timing
• Always
• Review the constant scan setting time.
• To secure sufficient excess time, correct the
value for "Constant scanning" and "Low Speed
Program Execution Time" in the PLC Parameter
dialog box.
RUN:
On
ERR.:
On
CPU Status:
Continue
Qn(H)
QnPH
QnPRH
QnU
LCPU
[PRG. TIME OVER]
• The low speed program execution time specified
in the PLC RAS setting of the PLC parameter
exceeded the excess time of the constant scan.
â– Collateral information
• Common information: Time (value set)
• Individual information: Time (value actually
measured)
â– Diagnostic Timing
• Always
Qn(H)
QnPH
QnPRH
[PRG. TIME OVER]
The program scan time exceeded the constant
scan setting time specified in the PLC RAS setting
of the PLC parameter.
â– Collateral information
• Common information: Time (value set)
• Individual information: Time (value actually
measured)
â– Diagnostic Timing
• Always
• Review the constant scan setting time in the
PLC parameter so that the excess time of
constant scan can be fully secured.
Q00J/Q00/Q01
5011
[PRG. TIME OVER]
The scan time of the low speed execution type
program exceeded the low speed execution watch
time specified in the PLC RAS setting of the PLC
parameter dialog box.
â– Collateral information
• Common information: Time (value set)
• Individual information: Time (value actually
measured)
â– Diagnostic Timing
• Always
Read the individual information of the error using
the programming tool to identify the numeric value
(time). Check the value and shorten the scan time.
Change the low speed execution watch time in the
PLC RAS setting of the PLC parameter dialog box.
Qn(H)
QnPH
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals