12.1 Error Code List
12.1.8 Error code list (6000 to 6999)
6020
[OPE. MODE DIFF.]
At power-on/reset, the RUN/STOP switch settings
of the control system and standby system are not
the same in a redundant system.
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
Set the RUN/STOP switches of the control system
and standby system to the same setting.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnPRH
6030
[UNIT LAY. DIFF.]
• In a redundant system, the module configuration
differs between the control system and standby
system.
• The network module mode setting differs
between the two systems.
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information: Module No.
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/At tracking cable
connection/At operation mode change
• Match the module configurations of the control
system and standby system.
• In the redundant setting of the network
parameter dialog box, match the mode setting of
System B to that of System A.
6035
[UNIT LAY. DIFF.]
In a redundant system, the CPU module model
name differs between the control system and
standby system.
(This can be detected from the standby system of
the redundant system.)
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/At tracking cable
connection/At operation mode change
Match the model names of the control system and
standby system.
6036
[UNIT LAY. DIFF.]
A difference in the remote I/O configuration of the
MELSECNET/H multiplexed remote I/O network
between the control system and standby system of
a redundant system was detected.
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information: Module No.
• Individual information:-
â– Diagnostic Timing
• Always
Check the network cables of the MELSECNET/H
multiplexed remote I/O network for disconnection.
6040
[CARD TYPE DIFF.]
In the redundant system, the memory card
insertion status (inserted/not inserted) differs
between the control system and standby system.
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
Match the memory card insertion status (inserted/
not inserted) of the control system and standby
system.
6041
[CARD TYPE DIFF.]
In the redundant system, the memory card type
differs between the control system and standby
system.
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
Match the memory card types of the control
system and standby system.
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals