12
Operation
Outdoor unit model
PUMY-P60NKMU(-BS)
Operating
conditions
Ambient
temperature
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F] 21.1°C/— [70°F/—]
Outdoor 35°C/— [95°F/—] 8.3°C/6.1°C [47°F/43°F]
Indoor unit
No. of connected units
Unit
4
No. of units in operation 4
Model — 06×2/24×2
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe 2.5 [8-1/4]
Total pipe length 15 [49-1/4]
Fan speed — Hi
Amount of refrigerant kg [lbs-oz] 8.5 [18]
Outdoor unit
Electric current A 21.4 27.4
Voltage V 230
Compressor frequency Hz 45 56
LEV opening Indoor unit Pulse 171 (P06)/426 (P24) 215 (P06)/534 (P24)
Pressure High pressure/Low pressure MPa [psi] 2.83/0.94 [411/136] 2.93/0.66 [425/95]
Temp. of each
section
Outdoor unit
Discharge
°C [°F]
74 [165] 68 [154]
Heat exchanger outlet 38 [100] 3 [37]
Accumulator inlet 13 [55] 0 [32]
Compressor inlet 14 [57] −1 [30]
Compressor shell bottom 74 [165] 68 [154]
Indoor unit
LEV inlet 27 [81] 40 [104]
Heat exchanger inlet 10 [50] 61 [142]
4-2. STANDARD OPERATION DATA (REFERENCE DATA)