Check code
Abnormal points and detection methods Causes and check points
<63L equipped model (63LS non-equipped)>
(1) Low pressure (63L is in operation)
Abnormal if 63L operates (under-0.03MPa) during compressor
operation.
<63LS equipped model (63L non-equipped)>
(2) Low pressure (63LS is in operation)
Abnormal if 63LS operates (under-0.03MPa) during compressor
operation.
63L : Low pressure switch
63LS : Low pressure sensor
LEV : Linear expansion valve
SV1 : Solenoid valve
TH7 : Outdoor temperature thermistor
Defective operation of stop valve (not fully open)
Clogged or broken pipe.
Malfunction or locked outdoor fan motor
Short-cycle of outdoor unit
Dirt of outdoor heat exchanger
Remote controller transmitting error caused by noise interference
Contact failure of outdoor controller board connector
Defective outdoor controller board
Short-cycle of indoor unit
Decreased air ow, clogged lter, or dirt on indoor unit.
Malfunction or locked indoor fan motor.
Decreased air ow caused by defective inspection
of outdoor temperature thermistor (It detects lower
temperature than actual temperature.)
Indoor LEV performance failure
Malfunction of fan driving circuit
SV1 performance failure
Defective low-pressure sensor
Malfunction of low-pressure sensor input circuit on
outdoor conrtoller board
Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis Remedy
1300
Low pressure trouble
Yes
Yes
Yes
No
No
Yes
Yes
No
No
No
Is the outdoor stop valve (ball
valve) fully open ?
Does the the outdoor fan rotare
while the operation?
Does the indoor fan rotate while
the operation?
Is the indoor unit lter clogged?
Is the indoor unit short-cycled?
Open the stop valve (ball balve) fully.
Check the outdoor fan motor
Refer to "How to check the parts" on
outdoor unit servive manual.
Check the indoor fan motor
Refer to "How to check the parts" on
indoor unit servive manual.
Clean the lter.
Solve the short-cycle.
(short-cycled)
( lter clogged)
(no short-cycle)
(no clog)
Continue to the next page
Chart 1 of 3
36
OCH502C