Check code
5109
HIC piping temperature thermistor (TH2) open/short
Abnormal points and detection methods Causes and check points
Abnormal if TH2 detects to be open/short.
Open: -40 [-40°F] or less
Short: 90 [194°F] or more TH2:
HIC piping temperature thermistor
Disconnection or contact failure of connectors
Characteristic defect of thermistor
Defective outdoor controller board
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Diagnosis Remedy
The black square (■) indicates a switch position.
No
Yes
Yes
Yes
No
No
Is there any abnormality such
as a disconnection, looseness or
breakage?
Is the detected resistance normal?
Is the detected temperature normal?
Connect the wiring/connector properly.
Replace it in case of a breakage.
Replace the thermistor.
Replace the controller board
(Malfunction of thermistor circuit).
No abnormality
( A connector contact failure is suspected).
Check the wiring and connector connection of TH2.
Disconnect the connector to check the
resistance of TH2 using a tester.
Check a temperature of TH2.
ON
OFF
12345678
SW1 Setting
Display on LED1,2
Unit
-99.9 999.9
*F=(9/5)×°C+32
°C
The detected temperature of TH2 can be displayed by
an operation of SW1 on the outdoor controller board.
62