Mitsubishi PUMY-P60NKMU - Piping Temperature Thermistor Open;Short

Mitsubishi PUMY-P60NKMU
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check code
Abnormal points and detection methods Causes and check points
Abnormal if TH3 detects to be open/short.
(The open/short detection is disabled during 10 sec. to 10 min. after
compressor starts, during defrosting operation, or for 10 min. after
returning from the defrosting operation.)
Open: -40 [-40°F] or less
Short: 90 [194°F] or more TH3: Piping temperature thermistor
Disconnection or contact failure of connectors
Characteristic defect of thermistor
Defective outdoor controller board
Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Diagnosis Remedy
5105
Piping temperature thermistor (TH3) open/short
The black square () indicates a switch position.
No
Yes
Yes
Yes
No
No
Is there any abnormality such
as a disconnection, looseness or
breakage?
Is the detected resistance normal?
Is the detected temperature normal?
Connect the wiring/connector properly
Replace it in case of a breakage.
Replace the thermistor.
Replace the controller board
(Malfunction of thermistor circuit).
No abnormality
( A connector contact failure is suspected).
Check the wiring and connector connection of TH3.
Disconnect the connector to check the
resistance of TH3 using a tester.
Check a temperature of TH3.
ON
OFF
12345678
SW1 Setting
Display on LED1,2
Unit
-99.9 999.9 °F
The detected temperature of TH3 can be displayed by an
operation of SW1 on the outdoor controller board
60
OCH502C