2-3. UNIT SPECIFICATIONS
(1) Method for identifying MULTI-S model
■
Indoor unit < When using Model 30 >
■
Outdoor unit <When using model 60 >
(2) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*10 - 46°C DB [50 - 115°FDB] : In the case of connecting PKFY-P06/P08 type indoor unit.
P L F Y - P 30 N B M U - E PU M Y - P 60 N
K M U -BS
PAC type
Frequency
conversion
controller
Refrigerant
R410A/R22
commonness
Refrigerant
R410A
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
Indicates equivalent
to Cooling capacity
Power supply
N: Single phase
208/230V 60Hz
Power supply
N: Single phase
208/230V 60Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C : Ceiling suspended type
M : Ceiling cassette type
F : Floor standing type
Outdoor unit
model type
Sub-number
Unit model type
UL model
M-NET control
M-NET control
UL model
Salt proof
type
Frequency
conversion
controller
Outdoor unit
MULTI-S
Cooling
W.B. 15 - 24°C [59 - 75°F]
Heating
D.B. 15 - 27°C [59 - 81°F]
:%í&>í)@
Indoor-side intake air temperature
Outdoor-side intake air temperature
'%í&>)@
(3) Guaranteed voltage
198 - 253V, 60Hz
Ŷ In the case of connecting fresh air type indoor unit
air type indoor
Capacity of Fresh
Cooling
Heating
Indoor-side and Outdoor-side
P30
D.B.21 - 43:[70 - 109°F] **
W.B.15.5 - 35:[60 - 95°F]
'%í - 20:[14 - 68°F] ***
intake air temperature
P54
D.B.21 - 43:[70 - 109°F] **
W.B.15.5 - 35:[60 - 95°F]
'%í:[23 - 68°F] ***
** Thermo-off (FAN-mode) automatically starts if the outdoor temp. is lower than 21:D.B.[70°FD.B.].
***Thermo-off (FAN-mode) automatically starts if the outdoor temp. is higher than 20:D.B.[68°FD.B.].