Check code
Abnormal points and detection methods Causes and check points
Abnormal if TH6 detects to be open/short.
(The open/short detection is disabled during 10 sec. to 10 min. after
compressor starts, during defrosting operation, or for 10 min. after
returning from the defrosting operation.)
Open: -40 [-40°F] or less
Short: 90 [194°F] or more TH6:
Low-pressure saturated temperature thermistor
Disconnection or contact failure of connectors
Characteristic defect of thermistor
Defective outdoor controller board
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Diagnosis Remedy
5102
Low-pressure saturated temperature thermistor (TH6) open/short
The black square (■) indicates a switch position.
No
Yes
Yes
Yes
No
No
Is there any abnormality such
as a disconnection, looseness or
breakage?
Is the detected resistance normal?
Is the detected temperature normal?
Connect the wiring/connector properly.
Replace it in case of a breakage.
Replace the thermistor.
Replace the controller board
(Malfunction of thermistor circuit).
No abnormality
( A connector contact failure is suspected).
Check the wiring and connector connection of TH6.
Disconnect the connector to check the
resistance of TH6 using a tester.
Check a temperature of TH6.
ON
OFF
12345678
SW1 Setting
Display on LED1,2
Unit
-99.9 999.9 °F
The detected temperature of TH6 can be displayed
by an operation of SW1 on the outdoor controller
board
59