EasyManua.ls Logo

Mitsubishi PUMY-P60NKMU - Outdoor Power Board

Mitsubishi PUMY-P60NKMU
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
90
Outdoor power board
PUMY-P60NKMU
PUMY-P60NKMU-BS
Brief check of POWER MODULE
* Usually, each point is in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
1.Check of DIODE circuit
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2.Check of IGBT circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note:The marks, L1 , L2 , L3 , N1 , N2 , P1, P2 , U , V and W
shown in the diagram are not actually printed on the board.
CNAC1, CNAC2
203/230 V AC
Connect to the out-
door controller circuit
board (CNAC)
NI, LI
Voltage of 208/230 V AC
is input (Connect to the
terminal block (TB1))
EI, E4
Connect to
the earth
DCL1, DCL2
Connect to DCL
P2
Connect to the
smoothing capacitor
CB +
U/V/W
Connect to the compres-
sor (MC) Voltage among
phases: 10 V-180 V AC
CNDC
280-380 V DC (1+, 3-)
Connect to the outdoor
controller circuit board
(CNDC)
E2, E3
Connect to the earth
CN52C
52C driving signal
Connect to the outdoor
controller circuit board
(CN52)
CN2
Connect to the outdoor controller circuit board (CN2)
1-5: Transmitting signal to outdoor controller circuit
board (0-5 V DC)
2-5: Zero cross signal (0-5 V DC)
3-4: 18 V DC
6-5: 16 V DC
7-5: 16 V DC
N2
Connect to the smoothing
capacitor CB -
CN4
Connect to the outdoor
controller circuit board (CN4)
OCH502C

Table of Contents