EasyManua.ls Logo

Mitsubishi PUMY-P60NKMU - Page 41

Mitsubishi PUMY-P60NKMU
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check code
1302
High pressure trouble
Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis Remedy
No
Is the voltage normal?
Is it free from any trace of over-
heating or burning?
Replace the indoor controller board.
Check the voltage and appearance of the
indoor controller board.
Check the resistance of SV1.
Chart 3 of 4
No
No
Yes
Yes
Yes
Continued from the previous page
Is there a resistance detected?
Is there a resistace detected?
Replace the TH7.
Replace the indoor LEV.
Disconnect the indoor LEV wiring to check
the resistance.
Continue to the next page