3 - 14                   3 - 14 
MELSEC-Q 
3   OUTPUT MODULE SPECIFICATIONS 
3.13 QY71 Transistor Output Module (Sink Type) 
Type 
Specifications 
Transistor output module (Sink type) 
QY71 Appearance 
Number of output points  32 points 
 
Isolation method  Photocoupler 
Rated load voltage  5/12VDC (+25/-10%) 
Maximum load current  16mA/point, 512mA/common 
Maximum inrush current  40mA, 10ms or less 
Output voltage at OFF  VOH: 3.5VDC (VCC=5VDC, IOH=0.4mA) 
Maximum voltage drop at ON  VOL: 0.3VDC 
Response time 
OFF to ON  0.5ms or less 
ON to OFF  0.5ms or less (resistive load) 
Surge suppressor  None 
Fuse  1.6A (unchangeable) (fuse capacity: 50A) 
Fuse blown indicator 
Provided (When a fuse blows, LED turns on and a signal is output to the 
CPU module.)  1 
External supply 
power 
Voltage  5 to 12VDC (+25/-10%) (ripple ratio within 5%) 
Current  MAX. 170mA (when 12VDC and all points are ON) 
Dielectric withstand voltage  560VAC rms/3 cycles (altitude 2000m) 
Insulation resistance  10MΩ or more by insulation resistance tester 
Noise immunity 
By noise simulator of 500Vp-p noise voltage, 1 s noise width  
and 25 to 60Hz noise frequency 
First transient noise IEC61000-4-4: 1kV 
Protection degree  IP2X 
Common terminal arrangement  32 points/common (common terminal: A01, A02) 
Number of occupied I/O points  32 points (I/O assignment is set as a 32-point output module.) 
Operation indicator  ON indication (LED) 
External connections  40-pin connector 
Applicable wire size 
0.088 to 0.3mm
2
 (For A6CON1 or A6CON4)  2 
Applicable connector  A6CON1, A6CON2, A6CON3, A6CON4 (optional) 
Internal current consumption 
(5VDC) 
150mA (TYP. all points ON) 
Weight 0.14kg 
 
External connection  Pin-Outs 
Pin 
No. 
Signal 
No. 
Pin 
No. 
Signal 
No. 
 
 
Module front view 
B20 Y00 A20 Y10 
B19 Y01 A19 Y11 
B18 Y02 A18 Y12 
B17 Y03 A17 Y13 
B16 Y04 A16 Y14 
B15 Y05 A15 Y15 
B14 Y06 A14 Y16 
B13 Y07 A13 Y17 
B12 Y08 A12 Y18 
B11 Y09 A11 Y19 
B10 Y0A A10 Y1A 
B09 Y0B A09 Y1B 
B08 Y0C A08 Y1C 
B07 Y0D A07 Y1D 
B06 Y0E A06 Y1E 
B05 Y0F A05 Y1F 
B04 Vacant A04 Vacant 
B03 Vacant A03 Vacant 
B02 
5/12 
VDC 
A02 COM 
B01 
5/12 
VDC 
A01 COM 
 
1: Fuse blown is not detected when the external power supply is shut off. 
2: When using A6CON2 or A6CON3, refer to Chapter 7. 
 
QY71
5/12VDC
16mA
QY71
01234567
89ABCDEF
01234567
89ABCDEF
FUSE
A20
A19
A18
A17
A16
A15
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
B20
B19
B18
B17
B16
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1