Power supply
29
04/99 AWB 2700-1311 GB
The C signal is the reference signal. It is used to
determine the reference position for subsequent
positioning tasks.
Figure 13: Reference signal
In most incremental encoders, the reference signal
occurs once every turn of the encoder, although
several signals will be output over the entire travelling
distance . You should therefore determine the
validity of the signal using an additional signal (limit
switch signal) . Set up the validity range so that no
other reference signal occurs within this range.
A function block (“IncEncoder”) is provided for
processing the input signals of an incremental
encoder. One incremental encoder may be
connected to each PS 4-300..
1 signal =
1 encoder rotation
Track C
(reference signal)
Limit switch signal
Note!
The function block “IncEncoder” is described in
the manual “Language elements for
PS 4-150/-200/-300 and PS 416“
(AWB 2700-1306 GB).