90
04/99 AWB 2700-1311 GB
General EMC specifications for automation equipment
Emission EN 55 011/22 Class A
Interference immunity
ESD EN 61 000-4-2 Contact discharge
Air discharge
4 kV
8 kV
RFI ENV 50 140 AM/PM 10 V/m
Burst EN 61 000-4-4 Mains/digital I/O
Analog I/O, fieldbus
2 kV
1 kV
Surge ENV 50 142 Digital I/O, asymmetrical
Mains DC, asymmetrical
Mains DC, symmetrical
Mains AC, asymmetrical
Mains AC, symmetrical
0,5 kV
1 kV
0.5 kV
2 kV
1 kV
Immunity to line-
conducted interference
ENV 50 141 AM 10 V