IP67 Digital I/O Modules for EtherNet/IP
I/O messaging
The firmware embedded in the HarshIO 600 eIP supports up to a maximum of 8 I/O connections. Fewer
connections allow faster data I/O update rates (RPI value).
I/O Connections:
- Module supports 2 Transport Class 1 I/O connections (Cyclic and Change-Of-State triggers):
o 1x Exclusive Owner
Unicast and Multicast (TO) connection
Unicast (OT) connection
o 7x Listen Only or Input Only
Multicast (TO) connection