PRODUCT TECHNICAL MANUAL
FONOMAC 3
V2.20 – 06/2012
26
MTELFONOMAC3220_EN
4.8. Test calls
The telephone must periodically make a test call in order to ensure it is working properly. This way, it is
guaranteed that it will work properly in case of entrapment. This test call must be made at least once every three
days. The destination number can be programmed (Parameter ID_04: Test phone number).
Test calls can be received either in manual or automatic mode.
MANUAL MODE: Once the telephone has been picked up at the call centre, the procedure will be similar to that of
receiving alarms; that is to say, the test call must be confirmed by pressing key (digit) “4”. If not correctly
confirmed, Fonomac 3 will try calling the same number after 30 minutes.
In this case, there must be a line to receive test calls and another one for real alarms. Otherwise, the call centre
would not be able to differentiate one type of call from another, except for Fonomac 3+ which is able to
distinguish them by means of the voice messages.
AUTOMATIC MODE: It will be run using a PC connected to the test call receiving line. In this case, the line can be
the same as the alarm receiving line, although the use of different lines is recommended. It requires the Alarm
Management Software (FonoPC) and modem (not included in Fonomac 3).
N.B.: If ID_33 “Test after Reset” parameter is activated, a test call will automatically be made every time the
telephone is reset.
4.9. Information the rescue service must have
The Rescue Service must have the following information:
Log including building addresses and telephone numbers of the corresponding alarm systems.
Per building:
o Address and location of each of the lifts, identified by their corresponding numbers (included in
Appendix B).
o Descriptions of means to access trapped passengers (included in Appendix B).
o All the special risks concerning the building entrance and lift access (included in Appendix B).
List of authorised personnel to perform a rescue operation and their corresponding authorisation codes to
clear the Alarm.
Periodic test log.
Automatic test log.
Alarm history log including cause of the alarm, their statuses with date and time, authorised rescuer to
clear the Alarm.
4.10. Information to the be supplied to the owner
The installer must inform the installation’s owner about the following:
The installation’s owner must ensure that the lift connects to the rescue service.
The information to be transmitted to the rescue service. See the corresponding Appendix.
The need to always keep the alarm equipment in operation in order to provide bidirectional communication
with a rescue service.
The need to cut the lift’s power supply if the bidirectional communication system is out of order.
The regular check-up of the verbal response from the rescue service, by using the device(s) for initiating
the alarm (manual test).
The information to use the alarm systems.
The system’s minimum maintenance requirements.
The information on how to change the dialling parameters, for example, telephone numbers, if they are
included in the alarm equipment.