Figure 25 Junction Box Figure 26 Junction Box Electrical Connections
Iftheremotesensorisnoteasilyaccessed,itisbestpracticetoinstalltubingthatcanbeusedtoapplycalibrationgasfrom
thedevicedisplay.RoutethetubingtotheULTIMAX5000GasMonitor,ensuringthattherearenokinks,leaksorother
obstructions.Securethistubingnearthemonitor.
3.6 ElectricalPowerConnections
3.6.1 ElectricalWarnings-ReadbeforeConnectingPower
WARNING!
BeforewiringtheULTIMA
X5000transmitter,disconnectthepowersourcesupplyingthetransmitterandensureno
hazardousatmospherepresent;otherwise,electricalshockorignitionofahazardousatmospherecouldoccur.
Installwiringinaccordancewiththeelectricalcodeofthecountryinuse,thelocalauthorityhavingjurisdictionand
theseinstallationinstructions,asapplicable.
DonotmakeanyconnectionstotheULTIMA
X5000mainboardorjunctionboxinput,output,andrelayconnections
whileunderpower.Makingconnectionsunderpowercouldleadtoelectricalshockorignitionofahazardous
atmosphere.
ULTIMA
X5000withrelaysarenotapprovedfornon-incendivewiringmethods.Useofnon-incendivewiringmethods
couldleadtoignitionofahazardousatmosphere.
Ensurethatwateranddirtarenotabletoentertheunitviathewireorconduit.Iftheunitisinstalledinalocationknown
tobewetordamp,itisgoodpracticetolooporbendtheentryintotheunitthatpreventswaterincursion.
Theinternalgroundingterminallocatedinthebaseofthetransmitterenclosuremustbeusedforequipment
grounding.Theexternalgroundingterminalisonlytobeusedasasupplementalbondingconnectionwherelocal
authoritiespermitorrequiresuchaconnection.
Aspartoftheproductcertification,itwasverifiedthatoptionalcommunicationfunctionsofthisgasdetection
instrumentwhileoperatingatthemaximumtransactionratedonotadverselyaffectthegasdetectionoperationand
functionsoftheinstrument.Theproductcertification,however,doesnotincludeorimplyapprovaloftheSafeSwap
feature,communicationsprotocolorfunctionsprovidedbythesoftwareofthisinstrumentorofthecommunications
apparatusandsoftwareconnectedtothisinstrument.
Followthewarningsbelowwhenremovingorreplacingsensors.ReferenceFigure3forcomponentoverview.
23 Ultima X5000 Gas Monitor US
3 Installation

Other manuals for MSA ULTIMA X5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MSA ULTIMA X5000 and is the answer not in the manual?

MSA ULTIMA X5000 Specifications

General IconGeneral
Ingress ProtectionIP66/67
SensorsElectrochemical, infrared
CommunicationHART, Modbus
Target GasesCombustible gases, toxic gases, oxygen
ApprovalsATEX, IECEx, UL, CSA, SIL 2