7.23.3 LOP – Test procedures
Preconditions
☑ Engine is stopped and starting disabled.
Preparatory steps
1. Connect battery in accordance with battery
manufacturer's instructions.
2. Switch master power switch to ON.
3. Switch on engine management system
ECS-5.
Result: • LOCAL OPERATION pushbutton (1) is il‐
luminated brightly (local control mode is
active);.
Switching between Local and Remote mode (automatic on-board network)
1. Press LOCAL OPERATION pushbutton (1).
Result: • LOCAL OPERATION pushbutton (1) flashes: Setting does not correspond with feedback signal from
Engine Control Unit.
• LOCAL OPERATION pushbutton (1) is illuminated at basic brightness: Remote mode active.
2. Press LOCAL OPERATION pushbutton (1) again.
Result: LOCAL OPERATION pushbutton (1) is illuminated brightly (Local mode is active);.
MW15550/06E 2012-02 | Task Description | 245