4.5Wheretoinstallthedehumidier
Selectaplacewherethedehumidiercausestheleastdisturbancetothecold-storageroomactivities,while
allowingformaintenanceworksuchasprocesslterreplacement.
Whentheunitisinstalledonabaseframe,thebaseframemustbedesignedinsuchawaythatitcaneasilybe
removedfromthecoldstore/freezer.Makesureopeningsforforkliftareincluded.
Thedehumidiermustbeplacedsothatthereisnoriskoftheprocessintakeandltericingup.Icenormally
formsnearthedoorsandair-locksofthecoldstorewherewarm,humidairowsin.
Installthedehumidierinsuchawaythatthereactivationairandwetairductsareasshortaspossible,max
1.5m.Seesection4.7,Installationexamplescoldstorageroom(freezer).
4.6Ducting
4.6.1Generalrecommendations
NOTE!Vibrationreduction.Ifthereisaneedtoforreductionofvibrationsfromthedehumidier,contactMunters
forinstructions.RefertostandardEN1299+A1:2008.
Duetothecoldsurroundingsandriskoffreezing,itisvitalthatallductingareinstalledaccordingto
instructions.Seealso4.7,Installationexamplescoldstorageroom(freezer).
Tofacilitateeasytransferofthedehumidieroutofthecold-storageroomforservice,allductconnections
shouldbeeasilydisassembled.Shouldthedehumidier,despitethisrecommendation,beinstalledinsucha
waythatitcannotbeeasilyremovedforservice,itisimportantthattheminimumservicespacerequirements
aremet,see8.1,Dimensionsandservicespace.Avapour-tightconnectionbetweenthewallandtheductisvital.
Preferably,polyurethanefoamshouldbeusedifthetemperatureissufcientlyhighduringapplication.
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing
recommendationsshouldbeobserved:
Thelengthofductworkshouldbekeptasshortaspossibletominimisestaticairpressurelosses.
Tomaintainperformance,allrigidprocessorreactivationairductworkjointsmustbeairandvapour
tight.
Thedesignoftheductconnectionsshouldfacilitateeasydisconnectionoftheunitforserviceoutside
thecold-storageroom.
Condensationeasilybuildsupontheinsideoftheductduetothehighhumidityofthereactivationair.
Toavoidcondensation,theductworkmustbeinsulated.
Theprocessairductworkshouldbeinsulatedtopreventcondensationfromdevelopingontheoutside
oftheductwheneverthetemperatureoftheairwithintheductfallsbelowthedewpointoftheambient
airthroughwhichtheductworkisrouted.
Thewetairleavingthedehumidierwilleasilycausecondensationontheinsideoftheductwallsdueto
thehighmoisturecontent.Thismustbeavoidedbyinsulatingtheducts.
Ensurethataccessforoperationandservicingisnotrestrictedwhendesigningandinstallingducting.
Formoreinformation,seesection8.1,Dimensionsandservicespace.
Toreducenoiseand/orvibrationbeingtransmittedalongrigidductwork,goodquality,airtightexible
connectionsshouldbetted.
Ductsmounteddirectlyontothedehumidiershouldbeadequatelysupportedtominimisetheloadand
stressduetotheweightandmovementoftheducting.