IceDry800/1400
CA CA
CA
UTION! UTION!
UTION!
Donotrestarttheunitwithoutrstleavingthereactivationheateronfor12hours.Seriousdamagetotheunitcan
betheresult.Withoutimmediateactionthereisariskthattherewillbeicebuild-upinthereactivationcircuit.
Toavoidtheriskforicetobuildup,theinandoutletopeningshavetobeblockedsonomoisturecanenter
thecircuitandcondensateandfreezeup.Withhighhumidityvaluesoutsidethiswillcreateaproblemwithin
afewhours.
ContactMuntersServicetodiscussthebestsolutionhowtominimisetheeffectsofapowersupplyfailure.
5.5.4Stop
1.Operatethemodeswitchtothe“0”positionandcheckthatbothreactivationheaterindicatorsgoout.
NOTE!Inorderfortheunittocooldown,thereactivationairfan,processairfanandthedrivemotorwillcontinue
torun(aftertheunithasbeenswitchedoff)untilthetemperaturehasfallenbelow50°C.
2.Checkthatwhenthereactivationairtemperaturefallsbelow50°C,theprocessairfan,reactivationfan
anddrivemotorindicatorsgooutandthatthepowerindicatorremainson.
CA CA
CA
UTION! UTION!
UTION!
Duringstand-by(themodeswitchinposition0)themainpowerswitchmustalwaysbeontoavoidbuildupof
iceinsidetheunit.
3.Inordertodissipateanyresidualheat,thereactivationairfanandtherotordrivemotorwillcontinueto
rununtilthereactivationtemperaturehasfallenbelowapproximately50°C.
4.Checkthatthereactivationairfanandthedrivemotorstoponcethereactivationtemperaturehasfallen
belowapproximately50°C.Afewminutesdelayisnormal.
20Operation190TGB-1037-G1307