42 NPE Service Manual
4.7.14 Error occurrence history display
1. At the <Normal operation mode> or <Error display mode>, press the [Info] button for over 2 seconds to access the error history mode.
The most recent error will be displayed first.
2. When the [+] / [-] button is pressed, the error history can be searched. A total of 10 errors are stored in memory and are labeled from 0 to 9
with 0 being the most recent error.
3. Whenever the [Info] button is pressed, the previous error occurrence time difference(unit time, maximum 9999 hr) and the sub error code
are toggled and displayed.
4. Pressing the [Reset] button for 5 seconds while in the <ERROR HISTORY DISPLAY MODE> displays “CLR” and deletes all the ERROR HISTORY
DATA.
5. Press the [Reset] button once to return to the <Normal operation mode>.
6. If there is no button input for 5 minutes, then it automatically returns to the <Normal operation mode>.
While in <ERROR HISTORY DISPLAY MODE> the first digit indicates the history of the error with 0 being the most recent. The remaining 3
digits indicate the error code. If there is no error history, a “0” will be displayed.
Passed time display: The time between the currently displayed error and the just previously generated error is displayed in 1-hr unit.
(0 is displayed if the error code is empty)
Ex) When the most recent error code is 615, the sub error code is 5, and 24 hours have passed since the error was generated.
When the Sub Error Code is 0(i.e., there is no sub error code), the display is as follows:
4.7.15 Service information display
1. At the <Normal operation mode>, press the [Diagnostic] button once to access the service information display.
2. Press [+] or[-] to navigate through the user parameters.
3. Item of current SERVICE Information Data is indicated as an alphabetical numbering on the first segment and relevant DATA value is
indicated at the 2nd, 3rd and 4th segment. (Alphabetical numbering A~Z are indicated and next ones and indicated as 1~9, then those
after that are indicated as symbols.)
4. Press the [Reset] button once to return to the <Normal operation mode>.
5. If there is no button input for 1 hour, then it automatically returns to the <Normal operation mode>.
6. The proper units are indicated with the LCD ICON for the applicable input items (Example: Water pressure - psi).
Item Description Display method
(A)Flow rate
Display of the current flow rate
Minimum display unit : 0.2
Gal/min or l/min
GPM flow rate display
ex ) 10.2GPM

Table of Contents

Other manuals for Navien NPE-240A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NPE-240A and is the answer not in the manual?

Navien NPE-240A Specifications

General IconGeneral
TypeTankless
Fuel TypeNatural Gas or Propane
Energy Factor0.97
Energy Efficiency97%
Voltage120V
Ignition TypeElectronic
Maximum Input199, 900 BTU/h
Water Connection Size3/4"
Gas Connection Size3/4"
Warranty15-year on heat exchangers, 5-year on parts, 1-year on labor
Dimensions17.3" W x 13.2" D x 27.4" H