74 NPE Service Manual
Error Code
Sub
Code
Function Self-diagnostic/Action
E407
1 Abnormal Hot water outlet thermistor (Open)
Check the thermistor.
Replace the thermistor.
2 Abnormal Hot water outlet thermistor (Short)
E421
1 Abnormal Cold water inlet thermistor (Open)
Check the thermistor.
Verify [C] value in DIAGNOSTIC mode.
Replace the thermistor.
2 Abnormal Cold water inlet thermistor (Short)
E432
1 Abnormal Cold water inlet2: thermistor (Open)
Check the thermistor.
Check thermistor voltage and resistance values.
Replace the thermistor.
2 Abnormal Cold water inlet2: thermistor (Short)
E434
1 Abnormal water adjustment valve. (Open)
Check the water adjustment valve.
2 Abnormal water adjustment valve. (Close)
E438 0 Abnormal circulation pump. ("A" models only)
Check the circulation pump.
Check water filter for blockage.
Check the flow sensor.
Check the cold water main line.
Set to Internal Recirculation mode and verify flow rate.
E439 0 Abnormal flow sensor
Check the flow sensor.
E441
1 Abnormal Hot water inlet2: thermistor(Open)
Check the thermistor.
2 Abnormal Hot water inlet2: thermistor(Short)
Replace the thermistor.
E445
1 Abnormal mixing valve(Open)
Check the mixing valve.
2 Abnormal mixing valve(Close)
E515
1~7 Abnormal communicatin between PCB and Ignitor.
Check the PCB.
8
Abnormal communication between PCB and
Ignitor
Check the PCB connection.
Check the Ignitor.
9 Abnormal communication between PCB and FAN
Check the PCB connection.
Check the Fan.
10 Abnormal monitoring device of PCB
Check the PCB connection.
Check the Dual Venturi.
11~12
Abnormal communication between PCB and Dual
Venturi
Check the PCB connection.
Check the Dual Venturi.
E517 0 Abnormal dip switch setting
Check the dip switches on the front panel and PCB.
E593 1 Abnormal panel key
Check the Panel.
E594
0
Abnormal input data from High limit switch of Heat
exchanger
Check the PCB.
1 Abnormal input data from exhaust sensor
Check the exhaust sensor wiring connection.
Check the exhaust sensor.
2 Abnormal input data from flame rod
Check the flame rod wiring connection.
Check the flame rod.
3~14 Abnormal memory of PCB
Check the PCB
15 Below the range of input data from Pressure sensor
Check the Pressure sensor wiring connection.
Check the output voltage of pressure sensor.
16 Over the range of input data from Pressure sensor

Table of Contents

Other manuals for Navien NPE-240A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NPE-240A and is the answer not in the manual?

Navien NPE-240A Specifications

General IconGeneral
TypeTankless
Fuel TypeNatural Gas or Propane
Energy Factor0.97
Energy Efficiency97%
Voltage120V
Ignition TypeElectronic
Maximum Input199, 900 BTU/h
Water Connection Size3/4"
Gas Connection Size3/4"