EasyManua.ls Logo

NetMan 102 plus - Menu Threshold Sens

NetMan 102 plus
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- ENGLISH -
- 86 -
Menu Threshold sens
/------------------------/
/ Threshold sens /
/------------------------/
Temperature max:100 degree C
Temperature min:20 degree C
Temp hysteresis:5 degree C
Humidity Max...:100 % RH
Humidity Min...:0 % RH
Hum hysteresis.:5 % RH
Press [Esc] to quit
With this menu is possible to set the alarm threshold for humidity and temperature sensors. When
exceeding the threshold a SNMP alarm trap will be sent, and then the trap will be sent for each
minute on which the alarm is active. The alarm ceases to be active when the outbound value
(temperature or humidity) is under the threshold with the degree of hysteresis that is configured.
(Example: with a maximum temperature of 100°C and 5°C hysteresis, the alarm is activated when
the temperature reaches 100°C and is removed when the temperature at 95°C).
Menu
Significato
Temperature max
Threshold for maximum temperature
Temperature min
Threshold for minimum temperature
Temp hysteresis
Hysteresis for removing temperature alarm (high and low)
Humidity max
Threshold for maximum humidity
Humidity min
Threshold for minimum humidity
Hum hysteresis
Hysteresis for removing humidity alarm (high and low)

Table of Contents

Related product manuals