6.3.2 Dierential (dIF)
Display
Description
Denes the compressor cut-in temperature when added to the set point (SP)
temperature during the Ready mode.
Considerations
If the dierential (dIF) is set too low, for example, less than 2.0°C the compressor may
cycle on the minimum compressor rest time (rt).
Range 0.0 to 9.9°C (0 to 18°F)
Global default 4.0°C (7°F)
6.3.3 Calibration 1 (CA1)
Display
Description Calibrates or adds an oset to temperatures measured by the appliance sensor.
Considerations Applied to all temperatures measured on the appliance sensor.
Range -4.0 to 4.0°C (-7 to 7°F)
Global default 0.0°C (0°F)
6.3.4 Compressor rest time (rt)
Display
Description
Denes the minimum time between compressor cycles.
The compressor rest time ensures that the pressures in the refrigeration system have
time to equalize during compressor o-cycles.
The compressor rest time (rt) helps to avoid the following:
passing peak current through the windings of the compressor motor
switching o the system on the thermal overload protection
short cycling of the system.
Considerations
If set too low, the compressor rest time may cycle on the set point (SP) and
dierential (dIF) temperatures or the saving set point (SSP) and saving dierential (Sd)
temperatures.
Range 1 to 30 minutes
Global default 3 minutes