CMS100 Product Manual, Issue 8
www.nexo.com Page 45
6.3.2 Dierential (dIF)
Display
Description
Denes the compressor cut-in temperature when added to the set point (SP)
temperature during the Ready mode.
Considerations
If the dierential (dIF) is set too low, for example, less than 2.0°C the compressor may
cycle on the minimum compressor rest time (rt).
Range 0.0 to 9.9°C (0 to 18°F)
Global default 4.0°C (7°F)
6.3.3 Calibration 1 (CA1)
Display
Description Calibrates or adds an oset to temperatures measured by the appliance sensor.
Considerations Applied to all temperatures measured on the appliance sensor.
Range -4.0 to 4.0°C (-7 to 7°F)
Global default 0.0°C (0°F)
6.3.4 Compressor rest time (rt)
Display
Description
Denes the minimum time between compressor cycles.
The compressor rest time ensures that the pressures in the refrigeration system have
time to equalize during compressor o-cycles.
The compressor rest time (rt) helps to avoid the following:
• passing peak current through the windings of the compressor motor
• switching o the system on the thermal overload protection
• short cycling of the system.
Considerations
If set too low, the compressor rest time may cycle on the set point (SP) and
dierential (dIF) temperatures or the saving set point (SSP) and saving dierential (Sd)
temperatures.
Range 1 to 30 minutes
Global default 3 minutes