The table below describes the values for activity frequency (AF).
Value Name Description
00 Low frequency 1 door opening or 1 motion count
01 Medium frequency 1 door opening or 3 motion counts
02 High frequency 2 door openings or 6 motion counts
03 Automatic
The controller runs continuously for 48 hours in the ready mode.
After 48 hours, the controller sets the value of the activity frequency to
0, 1, or 2.
Note
If AF is set to 3, the controller must run continuously for 48 hours to set the value of the
activity frequency. If power is lost during the 48 hour period, the controller restarts the
48 hour period.
The controller must complete the 48 hour period to determine the activity frequency
before starting the 1-day or 7-day learning period.
6.3.27 Fan set point (FSP)
Display
Description
Prevents excessive condensation on the evaporator in environments where warm, and
presumed humid, air is present by operating the evaporator fan.
If the fan set point (FSP) temperature is exceeded, the evaporator fan runs
continuously even if the door is opened.
On reaching set point (SP) temperature the evaporator fan resumes normal operation
and so switches o during door openings.
Considerations Not related to fan cycle on (FCO) or fan cycle o (FCF).
Range 1 to 60ºC (34 to 140ºF)
Global default 15ºC (59ºF)