Product Information
14
TemBreak PRO B_BE-UM-001-EN V1.1.0
B1600_BE Information
Frame / Model
Quantity
Unit
Condition
B1600N
B1600HL
Number of Poles
3, 4
3, 4
Nominal current ratings
I
CT
(A)
50°C
1600
1600
Trip unit ratings
Electrical characteristics
Rated maximum operational voltage
U
e
(V)
AC 50/60 Hz
690
690
(V)
DC
Rated insulation voltage
U
i
(V)
800
800
Rated impulse withstand voltage
U
imp
(kV)
8
8
Selectivity category
B
B
Rated short time withstand current
I
cw
(kA)
0.4 sec
20
20
Ultimate breaking capacity
I
cu
(kA)
690 Vac
20
45
(IEC, JIS, AS/NZS)
400 /415 Vac
50
85
240 Vac
85
125
Service breaking capacity
I
cs
(kA)
690 Vac
15
34
(IEC, JIS, AS/NZS)
400 /415 Vac
38
65
220 /240 Vac
65
94
Protection - Over Current Release types
Std Standard
Opt Optional
Not Available
BE 2 dials 10 pre-set characteristic curves
Std
Std
BE-G Ground Fault
Std
Std
BE Instantaneous only setting (ICB)
Std
Std
Installation (Std / Opt / ─ )
Std Standard
Opt Optional
Not Available
Front connection (FC)
Std
Std
Extension bar (FB)
Std
Std
Cable tunnel clamp (FW)
Rear connection (RC)
Opt
Opt
DIN rail adaptor
Withdrawable mechanism
Plug-in
Reverse supply connection possible to 440V
Dimensions
H
(mm)
370
370
W
(mm)
3 pole
210
210
4 pole
280
280
D
(mm)
191
191
T
(mm)
140
140
Weight
W
(kg)
3 pole
27
27
4 pole
35
35
Operation options (std / opt / - )
Std Standard
Opt Optional
Not Available
Toggle operation
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Motor operation TP-MC
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
4000
4000
Mechanical
Cycles
5000
5000

Table of Contents