EasyManua.ls Logo

NHP TemBreak PRO - Short Time Delay Protection (STD); Adjustment Isd (Current)

Default Icon
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Protection Settings
31
TemBreak PRO B_BE-UM-001-EN V1.1.0
Short Time Delay Protection (STD)
The short time protection is designed to protect against low level short circuits.
Adjustment I
sd
(Current)
The I
sd
trip threshold tolerance for STD protection is ±15%.
Adjustments to I
sd
can only be made by selecting a pre-defined curve. I
sd
trip threshold is defined as a multiple of I
r
as shown in the below table:
Short Time Delay Threshold Multiplier of I
r
Pre-defined curve number
Rating (I
n
)
1
2
3
4
5
6
7
8
9
10
B250
40 A
2.5
2.5
5
10
10
125 A
160 A
250 A
B400
250 A
2.5
2.5
5
10
10
10
10
400 A
B800
630 A
2.5
2.5
5
10
10
10
1.6
800 A
B1000
1000 A
2.5
2.5
5
8
8
8
1.6
B1250
1250 A
2.5
2.5
5
10
10
10
1.6
B1600
1600 A
2.5
2.5
5
10
10
10
1.6
Short Time Delay Settings
Description
S
I
sd
(x I
r
)
Short Time Delay protection threshold
t
sd
(ms)
Short Time Delay

Table of Contents