EasyManua.ls Logo

NHP TemBreak PRO - Annex B - Time Current Curves; B250_BE - In 40 A

Default Icon
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
TemBreak PRO B_BE-UM-001-EN V1.1.0
Annex B - Time Current Curves
B250_BE I
n
40 A
LTD pick up current I
r
16 20 25 32 36 38 40 A (7 steps)
30A (fixed)
40A (fixed)
Instantaneous only
Standard curves 1 - 5
Additional special application curves next pages
Characteristic dial setting
1
2
3
4
5
6
7
8
LTD
t
r
(s)
11
21
21
5
7.5
1
2.5
-
@ 2 x I
r
@ 6 x I
r
@ 90A
@ 120A
-
STD
I
sd
2.5 x I
r
2.5 x I
r
5 x I
r
10 x I
r
10 x I
r
-
-
-
t
sd
(s)
0.1
0.1
0.1
0.1
0.2
-
-
-
INST
I
i
14 x I
r
(Maximum of 13 x I
n
)
250A
300A
520A
OCR options
Pre-Trip Alarm
(PTA)
I
p
0.8 x I
r
0.8 x I
r
t
p
(s)
40
40
Neutral Pole
Protection (NP)
I
N
1.0 x I
r
1.0
t
N
(s)
t
N
= t
r
t
N
= t
r
1, 2, 3, 4, 5