EasyManua.ls Logo

NI CompactDAQ cDAQ-917 Series - Using an Internal Source; Using an External Source; Routing Counter N Sample Clock to an Output Terminal; Counter N Internal Output and Counter N TC Signals

Default Icon
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-36 | ni.com
Chapter 5 Counters
Using an Internal Source
To use Counter n Sample Clock with an internal source, specify the signal source and the
polarity of the signal. The source can be any of the following signals:
DI Sample Clock
DO Sample Clock
AI Sample Clock (ai/SampleClock, te0/SampleClock, te1/SampleClock)
AI Convert Clock
AO Sample Clock
DI Change Detection output
Several other internal signals can be routed to Counter n Sample Clock through internal routes.
Refer to Device Routing in MAX in the NI-DAQmx Help or the LabVIEW Help for more
information.
Using an External Source
You can route any of the following signals as Counter n Sample Clock:
Any PFI terminal
Analog Comparison Event
You can sample data on the rising or falling edge of Counter n Sample Clock.
Routing Counter n Sample Clock to an Output Terminal
You can route Counter n Sample Clock out to any PFI terminal. The PFI circuitry inverts the
polarity of Counter n Sample Clock before driving the PFI terminal.
Counter n Internal Output and Counter n TC Signals
The Counter n Internal Output signal changes in response to Counter n TC.
The two software-selectable output options are pulse output on TC and toggle output on TC. The
output polarity is software-selectable for both options.
With pulse or pulse train generation tasks, the counter drives the pulse(s) on the Counter n
Internal Output signal. The Counter n Internal Output signal can be internally routed to be a
counter/timer input or an “external” source for AI, AO, DI, or DO timing signals.
Routing Counter n Internal Output to an Output Terminal
You can route Counter n Internal Output to any PFI terminal.
Frequency Output Signal
The Frequency Output (FREQ OUT) signal is the output of the frequency output generator.