May be due toDescriptionAlarm text on the displayAlarm
Any circuit breakers for F2040 off
Incorrect cable routing
Communication between the control board
and the communication board is interrup-
ted. There must be 22 volt direct current
(DC) at the switch CNW2 on the control
board (PWB1).
OU Com. error223
The fan cannot rotate freely
Defective control board in F2040
Defective fan motor
Control board in F2040 dirty
Fuse (F2) blown
Deviations in the fan speed in F2040.Fan alarm224
Sensor does not work (see section "Am-
bient temperature sensor")
Insufficient air circulation or heat ex-
changer
Blocked
If the fault persists during cooling, there
may be an insufficient amount of refriger-
ant.
Defective control board in F2040
Temperature deviation on the hot gas
sensor (Tho-D) twice within 60 minutes or
for 60 minutes continuously.
Continuously high hot gas230
F2040 not powered
Fault in the communication cable.
Communication fault with accessory boardCommunication error254
Sensor does not work (see section "Dis-
turbances in comfort")
Insufficient air circulation or blocked heat
exchanger
Defective control board in F2040
Too much refrigerant
Temperature deviation on the heat ex-
changer sensor (Tho-R1/R2) five times
within 60 minutes or for 60 minutes con-
tinuously.
High temperature in heat
exchanger
261
Can occur when 15V power supply to
the inverter PCB is unstable.
When IPM (Intelligent power module) dis-
plays FO-signal (Fault Output) five times
during a 60-minute period.
Power transistor too hot262
Incoming power supply interference
Service valve closed
Insufficient amount of refrigerant
Compressor fault
Defective circuit board for inverter in
F2040
Voltage from the inverter outside the para-
meters four times within 30 minutes.
Inverter error263
Open circuit in connection between
boards
Defective circuit board for inverter in
F2040
Defective control board in F2040
Communication between circuit board for
inverter and control board broken.
Inverter error264
Defective fan motor
Defective circuit board for inverter in
F2040
Continuous deviation on power transistor
for 15 minutes.
Inverter error265
Service valve closed
Loose connection sensor (BT15, BT3)
Defective sensor (BT15, BT3)
Too little refrigerant
Insufficient refrigerant is detected upon
start-up in cooling mode.
Insufficient refrigerant266
Defective circuit board for inverter in
F2040
Defective control board in F2040
Compressor fault
Failed start for compressorInverter error267
Sudden power failureOvercurrent, Inverter A/F moduleInverter error268
57Chapter 10 | Alarm listNIBE F2040

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2040 Series and is the answer not in the manual?

Nibe F2040 Series Specifications

General IconGeneral
SeriesF2040
RefrigerantR410A
COPUp to 5.0 (depending on model and operating conditions)
Sound Power Level Indoor UnitN/A (Requires separate indoor unit)
Operating Temperature Range Cooling+10°C to +43°C
Dimensions Indoor Unit (HxWxD)N/A (Requires separate indoor unit)
TypeAir Source Heat Pump

Related product manuals