May be due toDescriptionAlarm text on the displayAlarm
Cold weather conditions
Sensor fault
Temperature of BT28 below the value that
permits operation
Cold outdoor air271
Warm weather conditions
Sensor fault
Temperature of BT28 above the value that
permits operation
Hot outdoor air272
Open circuit or short circuit on sensor
input
Sensor does not work (see section "Dis-
turbances in comfort")
Defective control board in F2040
Sensor fault, heat exchanger in F2040(Tho-
R).
Sensor fault Tho-R277
Open circuit or short circuit on sensor
input
Sensor does not work (see section "Dis-
turbances in comfort")
Defective control board in F2040
Sensor fault, outdoor temperature sensor
in F2040 (Tho-A).
Sensor fault Tho-A278
Open circuit or short circuit on sensor
input
Sensor does not work (see section "Dis-
turbances in comfort")
Defective control board in F2040
Sensor fault, hot gas in F2040 (Tho-D).Sensor fault Tho-D279
Open circuit or short circuit on sensor
input
Sensor does not work (see section "Dis-
turbances in comfort")
Defective control board in F2040
Sensor fault, suction gas in F2040 (Tho-S).Sensor fault Tho-S280
Open circuit or short circuit on sensor
input
Sensor does not work (see section "Dis-
turbances in comfort")
Defective control board in F2040
Fault in the refrigerant circuit
Sensor fault, low pressure transmitter in
F2040.
Sensor fault LPT281
Outdoor module and indoor module are
not compatible.
Heat pump and indoor module do not work
properly together due to technical paramet-
ers.
Non-compatible air/water
heat pump
294
Open circuit or short circuit on sensor inputSensor fault, Sensor high pressure heat-
ing/low pressure cooling in F2040 (BP4).
Sensor fault BP4404
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board AA23 in F2040
NIBE F2040Chapter 10 | Alarm list58

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2040 Series and is the answer not in the manual?

Nibe F2040 Series Specifications

General IconGeneral
SeriesF2040
RefrigerantR410A
COPUp to 5.0 (depending on model and operating conditions)
Sound Power Level Indoor UnitN/A (Requires separate indoor unit)
Operating Temperature Range Cooling+10°C to +43°C
Dimensions Indoor Unit (HxWxD)N/A (Requires separate indoor unit)
TypeAir Source Heat Pump